Analisa Keandalan Sistem Distribusi 20kv di PT. PLN (Persero) Rayon Kudus Kota Menggunakan Metode Section Technique

Main Article Content

Mohammad Rexy Hanif
Titiek Suheta

Abstract

This study was made with the aim of calculating the reliability index of the 20 kV distribution system in APJ Kudus on KDS2 feeders, with a network length of 21.267 km and 5207 subscribers. Using the section technique method, which is a method that performs reliability evaluation by breaking the system into smaller parts, so that the possibility of errors can be minimized, and the time required is shorter. The calculation results show that the SAIFI value is 4.2705 times / year and the SAIDI value is 6.81167 hours / year. The SAIFI value is not in accordance with the SPLN standard which is 3.2 times / year, this is due to too long air ducts, external disturbances (rain, lightning, wind), and internal disturbances (human factors of equipment). However, the SAIDI value is in accordance with the SPLN standard, namely 21 hours / year

Article Details

How to Cite
Mohammad Rexy Hanif, & Titiek Suheta. (2020). Analisa Keandalan Sistem Distribusi 20kv di PT. PLN (Persero) Rayon Kudus Kota Menggunakan Metode Section Technique . Jurnal Intake : Jurnal Penelitian Ilmu Teknik Dan Terapan, 11(2), 56-63. https://doi.org/10.48056/jintake.v11i2.134
Section
Articles
Author Biography

Titiek Suheta, Institut Teknologi Adhi Tama Surabaya

Sistem Tenaga, Institut Teknologi Adhi Tama Surabaya, Surabaya

References

Yusuf, Ali. 2017. “Analisis Keandalan Sistem Distribusi 20 kV di PLN Rayon Sidareja”. Jurusan Teknik Elektro. Fakultas Teknik. Universitas Muhammadiyah Yogyakarta.

Partawan, Dyana Arjana dan Weking. 2014. “Studi Perbandingan Keandalan Sistem Distribusi 20 kV Menggunakan Metode Section Technique dan RNEA Pada Penyulang Renon”. Jurusan Teknik Elektro. Fakultas Teknik. Universitas Udayana

Aditya Mulianda. 2016. Analisis Keandalan Sistem Jaringan Distribusi PT. PLN (Persero) Banda Aceh Menggunakan Metode Section Technique. Jurusan Teknik Elektro dan Komputer. Fakultas Teknik. Universitas Syiah Kuala Banda Aceh.

Moch Fahrulrozi, Hadi Suyono, Abraham Lomi. 2018. Peningkatan Keandalan Sistem Distribusi dengan Relokasi Penempatan Fuse-Recloser Optimal Karena Injeksi Pembangkit Tersebar. Jurusan Teknik Elektro. Fakultas Teknik. Universitas Brawijaya Malang.

Aang Fras Setiawan. 2018. Analisa Studi Keandalan Sistem Distribusi 20 kV di PT. PLN (Persero) UPJ Mojokerto Dengan Menggunakan Metode (Failure Mode Effect Analysis) FMEA. Jurusan Teknik Elektro. Fakultas Teknologi Industri. Institut Teknologi Adhitama Surabaya

SPLN 59. 1985. Keandalan Pada Sistem Distribusi 20kV dan 6kV. Jakarta: Perusahaan Umum Listrik Negara.

Muhammad Wahid Muntasyir. 2017. “Studi Analisis Keandalan Sistem Distribusi 20 kV Pada PT.PLN (Persero) APJ Surakarta”. Jurusan Teknik Elektro. Fakultas Teknik. Universitas Muhammadiyah Surakarta.

Prikno Sinaga, Hardiansyah dan Purwoharjono. 2017. “Analisa Keandalan Sistem Distribusi Berdasarkan Metode Section Technique Pada PT.PLN (Persero) Area Pontianak”. Jurusan Teknik Elektro. Fakultas Teknik. Universitas Tanjungpura.

Alen Tri Maliky. 2020. Analisis Keandalan Sistem Distribusi 20kV Pada Penyulang Pejangkungan di PT PLN Pasuruan Menggunakan Metode Reliability Index Assesment. Jurusan Teknik Elektro. Fakultas Teknik. Universitas Negeri Surabaya.

Syahmi Nanzain dan Tri Wrahatnolo. 2017. Evaluasi Keandalan Sistem Jaringan Distribusi 20 kV Menggunakan Metode Reliability Network Equivalent Aproach (RNEA) di PT.PLN rayon Mojokerto. Jurusan Teknik Elektro. Fakultas Teknik. Universitas Negeri Surabaya.