Analisa Tahanan Isolasi Pada Transformator Daya 20 MVA Di Gardu Induk ULTG Ende
DOI:
https://doi.org/10.32492/jeetech.v5i1.5104Keywords:
Transformator, isolation resistance, Indeks Polarisasi, Delta Tangen, Break Down VoltageAbstract
Power transformers are the main equipment in the electrical power system that is directly related to the distribution of electricity. One of the most important parts of a power transformer is its insulation system. Over time and operation, the condition of the insulation can deteriorate, which can cause operational failures and damage to the transformer. The purpose of the study was to determine the condition of the quality of insulation resistance in power transformers. The method was a literature study used to deepen the material related to the research title and data collection at the ULTG Ende Substation. The data taken were the results of polarization index, tangent delta and breakdown voltage tests. Based on the analysis results, the polarization index value in 2020 on the primary-ground side was 1.21 and the primary-secondary side was 1.23, but in 2022 it increased to 1.27 and 1.28. The tangent delta calculation results in 2020 on the secondary side on the CLG insulation was 0.64% and in 2022 it was 0.58%, which showed a decrease in insulation (0.5% - 0.7%). For breakdown voltage in 2020 it was 42.2 kV and OLTC 32.4 kV and in 2022 it was 41.1 kV and OLTC was 31.4 kV.
References
R. Syahputra, “TRANSMISI DAN DISTRIBUSI TENAGA LISTRIK,” Long Range Plann., vol. 28, no. 4, hal. 131, 1995, doi: 10.1016/0024-6301(95)94318-s.
T. A. SAPUTRO, “ANALISIS HASIL PENGUJIAN TAHANAN ISOLASI TRANSFORMATOR DAYA BERDASARKAN HASIL UJI INDEKS POLARISASI, TANGEN DELTA, RASIO TEGANGAN, BDV(BREAK DOWN VOLTAGE),” hal. 1–26, 2018.
J. PLN Pusdiklat, “PEMELIHARAAN TRAFO ARUS (CT) DAN TRAFO TEGANGAN PT PLN (Persero) PUSDIKLAT 2009,” hal. 89, 2009, [Daring]. Tersedia pada: http://www.nber.org/papers/w16019.
M. F. Robbani, D. Nugroho, dan G. Gunawan, “Penentuan Kelayakan Tahanan Isolasi Pada Transformator 60 MVA Di Gardu Induk 150 kV Tegal Dengan Menggunakan Indeks Polarisasi, Tangen Delta, Dan Breakdown Voltage,” Elektrika, vol. 12, no. 2, hal. 60, 2020, doi: 10.26623/elektrika.v12i2.2721.
D. Almanda dan A. Ardiansyah, “Analisis Pengujian Tangen Delta Pada Bushing Trafo 150/20 Kv 60 Mva Di Gardu Induk Karet Lama,” Resist. (Elektronika Kendali Telekomun. Tenaga List. Komputer), vol. 5, no. 2, hal. 97, 2022, doi: 10.24853/resistor.5.2.97-102.
H. R. Febrijanto dan R. Hidayat, “Analisis Pengujian Tan Delta Pada Transformator Arus Di Gitet Tasikmalaya Bay Penghantar Bandung Selatan-1,” Teknokom, vol. 6, no. 2, hal. 86–95, 2022, doi: 10.31943/teknokom.v6i2.143.
F. Faturochman, “PENGUJIAN TINGKAT ISOLASI TRANSFORMATOR DAYA TEGANGAN 150/20 KV KAPASITAS 60 MVA PADA GARDU INDUK DENGAN METODE TANGENT DELTA,” 2018.
S. Riyanto, “Analisis Tahanan Isolasi Pada Transformator Di Gardu Induk 150 Kv Purwodadi,” hal. 10, 2021.
R. A. Efryansah et al., “ANALISIS KUALITAS TAHANAN ISOLASI PADA TRANSFORMATOR DENGAN PREVENTIVE MAINTENANCE DI GARDU INDUK GARUDA SAKTI,” 2023.
M. Ansori, “Analisa Kinerja Minyak Trafo Berdasar Hasil Uji Dissolved Gas Analysis (DGA) Dengan Metode Total Dissolved Combustible Gas (TDCG) Di PLTU MUARA KARANG,” JREEC (Journal Renew. Energy Electron. Control., vol. 03, no. 01, hal. 27–34, 2023, [Daring]. Tersedia pada: https://ejurnal.itats.ac.id/jreec.
Published
How to Cite
Issue
Section
Copyright (c) 2024 Titiek Suheta, Muhamad Zainudin Abdul Medjid, Khoirul Anwar

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.