ETAP-Based Voltage Profile Assessment and Tap-Changer Improvement of the 20 kV OSM Feeder

Authors

  • Salwa F. R. Tuasikal Politeknik Negeri Ambon, Ambon, Indonesia
  • Marceau Haurissa Politeknik Negeri Ambon, Ambon, Indonesia
  • Arnold J. Kastanja Politeknik Negeri Ambon, Ambon, Indonesia

DOI:

https://doi.org/10.32492/jeetech.v7i2.7211

Keywords:

ETAP, Load Flow, Medium-Voltage Feeder, Tap Changer

Abstract

This study assessed the voltage profile of the cascaded Karpan 1-Kuda-OSM 20 kV network in Ambon and evaluated transformer tap adjustment as a corrective action. Primary data from PT PLN (Persero) UP3 Ambon included single-line diagrams, conductor parameters, transformer ratings, feeder lengths, installed loads, and measured peak loads. The network was modelled in ETAP and solved by the Newton-Raphson load-flow method under installed-load and peak-load scenarios. Manual three-phase voltage-drop calculations were used to check the OSM segment. Before correction, the terminal voltage at LBS Wainitu was 19.12 kV under installed load and 19.32 kV under peak load. Across the 31.061 km cascaded path, the voltage drops were 0.51 kV (2.6%) and 0.34 kV (1.7%), respectively. Although both met the 5% radial-feeder criterion, the installed-load terminal voltage was only 0.12 kV above the 0.95 pu reference. A -2.5% primary fixed-tap adjustment on transformers T1 and T3 raised the sending voltage to 20.15 kV and 20.18 kV. Consequently, the terminal voltage increased by 0.53 kV to 19.65 kV and 19.85 kV. The correction improved voltage margin without materially changing the line-drop percentage, indicating that the dominant voltage deficit originated at the sending bus rather than in the OSM segment.

Downloads

Download data is not yet available.

References

M. A. F. Haurissa, M. Jamlaay, and L. M. Parera, “Evaluation of Voltage Profile in ETAP (Electric Transient and Analysis Program) at Ahuru Feeder 20 kV Medium Voltage Distribution,” International Journal of Science, Technology & Management, vol. 5, no. 2, pp. 460-466, 2024, doi: 10.46729/ijstm.v5i2.1066.

F. E. P. Surusa, Y. Andrean, and S. Humena, “Analysis of 20 kV Distribution Network Reconfiguration PLN ULP Marisa,” Jambura Journal of Electrical and Electronics Engineering, vol. 7, no. 2, 2025, doi: 10.37905/jjeee.v7i2.33150.

Y. E. P. Bachari, Y. Mohamad, T. I. Yusuf, and L. M. K. Amali, “Analysis of Voltage Drop and Power Losses on Medium Voltage 20 kV Distribution System Kotamobagu Area Supplied from PLTD Kotamobagu,” JEECS (Journal of Electrical Engineering and Computer Sciences), vol. 9, no. 1, pp. 79-88, 2024, doi: 10.54732/jeecs.v9i1.9.

N. Ristami and Rosdiana, “Voltage Drop Study on Medium Voltage Network System at PT PLN (Persero) UP3 Banda Aceh 20 kV Using ETAP Software,” Fidelity: Jurnal Teknik Elektro, vol. 7, no. 1, pp. 58-67, 2025, doi: 10.52005/fidelity.v7i1.261.

A. Hasibuan, F. Dani, Asran, and I. M. A. Nrartha, “Simulation and Analysis of Distributed Generation Installation on a 20 kV Distribution System Using ETAP 19.0,” Bulletin of Computer Science and Electrical Engineering, vol. 3, no. 1, pp. 18-29, 2022, doi: 10.25008/bcsee.v3i1.1151.

L. Adhere, I. Syafruddin, and E. P. Sinulingga, “Impact of Small Hydro Generation on Voltage Profile and Losses in 20 kV Distribution Network,” Journal of Physics: Conference Series, vol. 2193, no. 1, Art. no. 012034, 2022, doi: 10.1088/1742-6596/2193/1/012034.

M. A. Sobikin, “Analisis Drop Tegangan dan Manuver Jaringan pada Penyulang SGN11 dan Penyulang SGN14 Menggunakan Software ETAP 16.0.0,” CYCLOTRON, vol. 5, no. 1, pp. 35-40, 2022, doi: 10.30651/cl.v5i1.10638.

M. Y. Rofandy, A. Hasibuan, and Rosdiana, “Analysis of the Effect of Bank Capacitor Placement as Voltage Drop Increase in Distribution Network,” Andalasian International Journal of Applied Science, Engineering and Technology, vol. 2, no. 1, pp. 11-24, 2022, doi: 10.25077/aijaset.v2i1.32.

R. M. E. Suherman and M. Sunarhati, “Studi Perbaikan Kualitas Tegangan dan Rugi-Rugi Daya pada Penyulang Kulim dan Jelutung dengan Menggunakan Aplikasi ETAP 12.6,” Jurnal Teknik Elektro, vol. 9, no. 2, pp. 30-37, 2021, doi: 10.36546/jte.v9i2.390.

M. A. F. Haurissa, “Simulasi Aliran Daya Berbasis ETAP Menggunakan Metode Newton-Raphson pada Jaringan Distribusi 20 kV Penyulang Lateri 2 dan Lateri 3,” Jurnal ELKO (Elektrikal dan Komputer), vol. 4, no. 1, pp. 360-368, 2023, doi: 10.54463/je.v4i1.89.

W. H. Kersting, Distribution System Modeling and Analysis, 4th ed. Boca Raton, FL, USA: CRC Press, 2017.

H. Saadat, Power System Analysis, 3rd ed. Alexandria, VA, USA: PSA Publishing, 2010.

PT PLN (Persero), SPLN 72:1987: Spesifikasi Desain untuk Jaringan Tegangan Menengah (JTM) dan Jaringan Tegangan Rendah (JTR). Jakarta, Indonesia, 1987.

PT PLN (Persero) UP3 Ambon, “Single-line diagrams and operational data for the Karpan 1, Kuda, and OSM feeders,” internal technical data, Ambon, Indonesia, 2024.

Y. Ambabunga, L. D. Rumpa, and D. Patiung, “Analisis Jatuh Tegangan dan Rugi Daya pada Feeder (T2) PT PLN (Persero) ULP Rantepao Menggunakan ETAP 19.0.1,” Dynamic Saint, vol. 8, no. 1, pp. 100-104, 2023, doi: 10.47178/dynamicsaint.v8i1.2161.

Published

2026-11-11

How to Cite

[1]
Salwa F. R. Tuasikal, M. Haurissa, and Arnold J. Kastanja, “ETAP-Based Voltage Profile Assessment and Tap-Changer Improvement of the 20 kV OSM Feeder”, jeetech, vol. 7, no. 2, pp. 306-316, Nov. 2026.