Single-Tuned Passive Filter for Harmonic and Transformer Derating Mitigation at Airlangga University Distribution System

Authors

  • Wahyu Setyawan Universitas 17 Agustus 1945 Surabaya
  • Aris Heri Andriawan Universitas 17 Agustus 1945 Surabaya
  • Reza Sarwo Widagdo Universitas 17 Agustus 1945 Surabaya

DOI:

https://doi.org/10.32492/jeetech.v7i2.7208

Keywords:

Harmonic Distortion, Single Tuned Passive Filter, Transformer Derating, ETAP

Abstract

Harmonic distortion caused by nonlinear loads can increase transformer losses and reduce its effective operating capability, even when the transformer operates under relatively low loading conditions. This study evaluates harmonic distortion and transformer derating in the electrical distribution system of the Nanizar Zaman Joenoes Building at Airlangga University and investigates the effectiveness of a single-tuned passive filter in mitigating these effects. Field measurements were conducted at the main distribution panel connected to the secondary side of a 1.6 MVA, 20 kV/400 V transformer operating at approximately 20–22% loading. The measured voltage harmonic distortion remained below the adopted limit, while the measured current distortion indicated significant lower-order harmonic components, with TDD values of 18.61%, 15.23%, and 14.40% for phases R, S, and T, respectively. K-Factor-based analysis indicated an initial transformer derating of 15.00%. A 5th-order single-tuned passive filter was subsequently designed at 250 Hz with a reactive power rating of 114.4 kVAr, a capacitance of 2276 µF, an inductance of 0.178 mH, and a resistance of 0.00559 Ω. ETAP simulation showed that the proposed filter reduced THDi from 10.37% to 5.01%, improved the power factor from 66.37% to 86.21%, and reduced transformer derating from 15.00% to 3.48%. The main contribution of this study is the integrated evaluation of harmonic mitigation and transformer operating-capability recovery in a lightly loaded building distribution transformer. The results demonstrate the potential of a properly tuned passive filter to reduce harmonic-related transformer derating, while field validation under varying load conditions remains necessary

Downloads

Download data is not yet available.

References

P. A. Auliasari et al., “Transformasi Manajemen Energi di Gedung Perkantoran Modern melalui Teknologi Cerdas,” 2025.

M. Zubair and H. Tasmono, “Analisa Pengaruh Beban dan Suhu Lingkungan Terhadap Susut Usia Transformator Di Galaxy Mall 3,” 2023.

A. Fikry and P. Slamet, “Analisis Derating Transformator Distribusi Akibat Pembebanan Non-Linear di Universitas 17 Agustus 1945 Surabaya,” 2023.

A. Fadlli and A. H. Andriawan, “Analisa Harmonisa Pada Gedung Kuliah Bersama Universitas Airlangga,” 2022.

R. Sarwo Widagdo, K. Setyadjit, and I. Aula Wardah, “Analysis and Mitigation of Harmonics Distortion with Optimization Capacitor Banks and Single-Tuned Passive Filters,” Jambura Journal of Electrical and Electronics Engineering, vol. 204, 2022.

E. Permata and I. Lestari, “MAINTENANCE PREVENTIVE PADA TRANSFORMATOR STEP-DOWN AV05 DENGAN KAPASITAS 150KV DI PT. KRAKATAU DAYA LISTRIK,” Prosiding Seminar Nasional Pendidikan FKIP Universitas Sultan Ageng Tirtayasa, vol. 3, no. 1, pp. 485–493, 2020.

Ali Mahfud Shodar, “Analisis Penempatan Transformator Distribusi Berdasarkan Drop Voltage Pada PT. PLN (Persero) Distribusi Lamongan Menggunakan Software Etap 19.0,” Jurnal Teknik Mesin, Industri, Elektro dan Informatika, vol. 2, no. 4, pp. 49–61, Nov. 2023, doi: 10.55606/jtmei.v2i4.2888.

F. Saputra, “PENGUJIAN EFFISIENSI TRANSFORMATOR INTI FERRIT DI LABORATORIUM TEKNIK ELEKTRO UNIVERSITAS PGRI PALEMBANG,” vol. 3, no. 2, 2018.

Jhonson, M. Siburian, and J. Tekad, “STUDI ANALISIS KETAHANAN ISOLASI PADA TRANSFORMATOR DI GARDU INDUK LABUHAN,” 2021.

P. Vokasional and T. Elektro, “SISTEM MAINTENANCE TRANSFORMATOR 60 MVA PADA ELECTRIC ARC FURNACE (EAF) 7 SLAB STEEL PLANT 1 Irwanto,” 2020.

P. Meliansyah and D. Aribowo, “UJI TEGANGAN TEMBUS MINYAK ON LOAD TAP CHANGER DI GARDU INDUK 150KV RANGKAS BARU,” vol. 1, no. 4, 2022.

J. Ilham and S. Salim, “STUDI KARAKTERISTIK MINYAK NILAM SEBAGAI ALTERNATIF PENGGANTI MINYAK TRANSFORMATOR,” Jambura Journal of Electrical and Electronics Engineering, 2019.

E. R. Surbakti and M. Sj, “ANALISIS PENGARUH HARMONISA TERHADAP FAKTOR-K PADA TRANSFORMATOR,” 2015.

M. Al and E. Zondra, “ANALISIS HARMONISA MENGGUNAKAN FILTER PASIF PADA VSD DENGAN BEBAN MOTOR ELECTRICAL SUBMERSIBLE PUMP DI PT. CPI,” 2021.

Published

2026-11-09

How to Cite

[1]
Wahyu Setyawan, Aris Heri Andriawan, and Reza Sarwo Widagdo, “Single-Tuned Passive Filter for Harmonic and Transformer Derating Mitigation at Airlangga University Distribution System”, jeetech, vol. 7, no. 2, pp. 266-281, Nov. 2026.